Ứng dụng máy bơm, quạt và máy nén có đặc tính bậc hai. Chúng không có một chopper tích hợp (ứng dụng một góc phần tư). Chỉ tạo ra các sóng hài bậc thấp và tổn thất điện năng rõ ràng. Hiệu quả năng lượng, tốt cho môi trường.Dùng hệ thống quản lý tòa nhà; máy móc công nghiệp
Thông tin chi tiết về SINAMICS G120P, built-in and wall-mounted units, IP20/IP54/IP55 > PM230 Power Modules, 0.37 kW to 90 kW của SIEMENS
PM230 Power Modules, degree of protection IP54, frame sizes FSA to FSF (with operator panel)
 

Tóm tắt về sản phẩm SINAMICS G120P Built-In and Wall-Mounting Units 

Options with added value: for your applications in heating, ventilation and air-conditioning systems

 

Whether installed in the intake and exhaust fans of air-conditioning systems, in pumps for heating and cooling circuits, or in compressors for refrigeration units: SINAMICS G120P converters are ideally suited to meet every requirement of building management systems.
 

Flexible installation

Stay flexible: Due to their IP20 and IP55 degrees of protection, the PM230 Power Modules can not only be installed in the control cabinet, but can also be directly at the machine. And thanks to different EMC filters, they can be used both in the public power grid and in industrial networks.
 

Special functionality

A well-thought-out portfolio: Apart from standard functions such as setpoint specifications, on/off switching logic, protection and monitoring of machine, motor and converter, SINAMICS G120P also offers numerous industry-specific functions. These include the regulation of two or multiple zones and one fire protection mode which ensures the longest possible operation in an emergency.
 

Highlights at a glance – specially developed for your applications in building management systems

- Full control – Real-time clock with exact time stamp for error and warning logging, max. buffer time five days, automatic summer / winter changeover

- Freely programmable – Digital timers for the control of three selectable events depending on the weekday / hour / minute

SINAMICS G120P in the Building Technologies:

Power:

0,37 - 90 kW

Voltage:

3 AC 380 - 480 V

Control procedure:

U/f control with stator flux orientation, vector control without encoder

 

SINAMICS G120P – options with added value: for your industrial applications

Growing complexity of plants and globalization of markets: The drives of the SINAMICS G120P series always have the right answer for the special features of the process industry.
 

Simply practice-oriented

Usable and available worldwide – SINAMICS G120P is ready to meet your global requirements. And with the key functions of speed control, controlling range, efficiency and communication level, it ensures simple operation.
 

Maximum flexibility

Thanks to the upgraded PM330 Power Modules, you now have a complete series of SINAMICS G120P products at your disposal: in all sizes and across all voltage ranges, from 400 V to 690 V. A flexibly applicable and consistent approach, which minimizes your configuration and implementation overheads.
 

Reliably safeguarded

The new PM240P-2 Power Modules increases your process reliability: with integrated safety functionality up to the SIL3 level.

Highlights at a glance – specially developed for your industrial applications

The new Power Modules PM240P-2

- Process reliability – Utmost safety level thanks to Integrated safety functions, safe electronic switch-off (Safe Torque-off / Safe Stop 1)

- Robustness – Even for special operating conditions such as temperatures ranging from -10° C to 60° C and aggressive environments (resistance to pollutants)

- Cost saving – Increased energy efficiency with higher output voltage (98 %) through integrated dc link reactor
 

The innovated Power Modules PM330

- Enhanced flexibility – due to the new voltage level up to 690 V

- Saving space – allows compact control cabinets

- Robustness – through numerous functions such as output voltage sensing

- Total integration – the complete product series is available

SINAMICS G120P in the Process industry

Power:

11 - 630 kW

Voltage:

3 AC 380 - 480 V and 3 AC 500 - 690 V

Control procedure:

U/f control with stator flux orientation, vector control without encoder

 

Details on SINAMICS G120P built-in and wall-mounted devices

Power Modules

SINAMICS G120 Power Modules

Power Modules for industrial applications and building technology

 

Control Units

SINAMICS G120 Control Units

Control Units have been especially designed for pump, fan, compressor applications

 

Accessories

SINAMICS G120 Optionen

Supplementary system components for SINAMICS G120P


SINAMICS G120P Inverters > PM230 Power Modules, 0.37 kW to 90 kW

Offer a Comprehensive Range of Power Modules for pumps, fans and compressors Applications

 

Overview

  • Power modules for building management systems
  • Power modules for industrial applications
 

Power modules for building management systems

  • Low harmonic effects, low apparent current consumption, high power factor

  • IP55 degree of protection for direct on-site setup, longer cables possible due to reactors, operation of motors with low voltage strength via optional filters

  • Operation at ambient temperatures up to 60 °C

  • Integrated filters for use in public power grids and industrial environments

 

Power Modules PM230 (IP20)


Power Modules PM230 Frame size FSA up to FSF, IP20 Degree of protection

PM230 Power Modules in an IP20 degree of protection are available in six frame sizes in the following voltage and power range:
3AC380 … 480 V +/-10%, 0,37 … 75 kW

 

Power Modules PM230 (IP55)


Power Modules PM230 Frame size FSA up to FSF, IP55 Degree of protection

PM230 Power Modules in an IP55 degree of protection are available in six frame sizes in the following voltage and power range:
3AC380 … 480 V +/-10%, 0,37 … 90 kW

Using the SINAMICS G120P Cabinet units in degrees of protection IP20 up to IP54, the power range for wall-mounting devices can be increased up to 110 ... 630 kW.

  •  SINAMICS G120P Cabinet
 

Power modules for industrial applications

The new PM240P-2 Power Module

  • Process reliability: highest level of safety thanks to integrated safety functions and safe electronic shutdown (Safe Torque-Off / Safe Stop 1)

  • Robustness: also suitable for tougher environmental conditions such as temperatures from -10 °C to +60 °C and aggressive atmospheres (resistance to harmful substances)

  • Energy saving: increased energy efficiency with higher output voltage (98 percent) due to integrated DC link reactor


Power Modules PM240P-2 Frame size FSD up to FSF, IP20 Degree of protection

PM240P-2 Power Modules in an IP20 degree of protection are available in three frame sizes in the following voltage and power range:
3AC380 … 480 V +/-10%, 22 … 132 kW
3AC500 ... 690 V +/-10%, 11 ... 132 kW

 

The upgraded PM330 Power Module

  • Greater flexibility – with a new voltage level up to 690 V

  • Space-saving – facilitates compact control cabinets

  • Robustness – due to numerous functions such as output voltage recording

  • Integration – complete product range available


Power Modules PM330 Frame size FSGX and FSJX, IP20 Degree of protection

PM330 Power Modules in an IP20 degree of protection are available in two frame sizes in the following voltage and power range:
3AC380 … 480 V +/-10%, 160 … 560 kW
3AC500 ... 690 V +/-10%, 315 ... 630 kW

 


Chi tiết về sản phẩm SINAMICS G120P Built-In and Wall-Mounting Units > PM230 Power Modules, 0.37 kW to 90 kW

 

Overview

PM230 Power Modules are designed for applications involving pumps, fans and compressors with a quadratic characteristic. They do not have an integrated braking chopper (single-quadrant applications).
 

The PM230 Power Module only generates low line harmonics and apparent power losses. In addition to the energy-related advantages, the environmental stress is also reduced.
 

  • Line harmonics are reduced significantly.
    • The limit values of EN 61000‑3‑12 are complied with for RSCE > 250.
      RSCE is the short-circuit power ratio Ssc line/Sinverter acc. to EN 61000‑3‑12 and is identical to RSC acc. to IEC 60146‑1‑1 in the case of three-phase devices.
    • Additional components such as line reactors are not required and it is not permissible to use them. As a consequence, low envelope dimensions are obtained for space-saving designs.
  • The active power component is very high, i.e. the devices consume less current from the supply for the same drive power. As a consequence, smaller supply cables can be used.
  •  

Frame sizes FSA to FSF of the PM230 Power Module in degree of protection IP55 are available with integrated line filter class A for installations acc. to Category C2 and in accordance with EN 61800‑3. The PM230 Power Modules with integrated filter class B that are available as an alternative also comply with the conducted interference requirements for Category C1 in accordance with EN 61800‑3.
 

Frame sizes FSA to FSF of the PM230 Power Module in degree of protection IP20 are available with integrated line filter class A for Category C2 installations in accordance with EN 61800‑3, or without an integrated line filter.
 

The frame sizes FSA to FSC of the PM230 Power Module with degree of protection IP20, Push Through version, are available with integrated line filter class A for installations acc. to Category C2 as per EN 61800‑3 or without an integrated line filter.
 

PM230 Power Modules with integrated line filter class A or class B meet the EMC limit values up to a maximum cable length of 25 m (82 ft) with shielded cables between inverter and motor.
 

Unfiltered PM230 Power Modules with degree of protection IP20 with external line filter class B comply with EMC Category C1 with a cable length of 50 m (164 ft) between the converter and the motor. EMC Category C2 is complied with through the use of an additional output reactor for a cable length of 150 m (492 ft) (see output-side power components).
 

The line system configurations that are supported are symmetrical systems with grounded neutral point.

PM230 Power Modules in frame sizes FSA to FSC can be combined with the CU240E‑2 Control Unit 1). This enables the implementation of the STO safety function acc. to SIL 2.

PM230 Power Modules, frame sizes FSD to FSF, do not support Control Units with Safety Integrated. Safety functions can be implemented here by means of external switching devices.
 

1) More information on the CU240E‑2 Control Unit is available in Catalog D 31, Chapter SINAMICS G120. An adapter, article number 10055500 (ordered from and supplied by KnorrTec at www.knorrtec.com), is required to operate a PM230 Power Module with degree of protection IP55 in combination with a CU240E‑2 Control Unit and an IOP/BOP-2.
 

Note:

Shield plates and shield connection kits are available. These can be used in the wiring installation for the Control Units and Power Modules to ensure that it complies with EMC guidelines.
For more information, see Shield connection kits and shield plates for Control Units and Power Modules in section Supplementary system components.
 

Integration

 

PM230 Power Modules have the following connections and interfaces:

  • PM‑IF interface for connection of the PM230 Power Module and Control Unit. The PM230 Power Module also supplies power to the Control Unit using an integrated power supply.
  • Motor connection using screw-type terminals or screw studs
  • 2 PE/protective conductor connections


PM230 Power Modules communicate with the Control Unit via the PM-IF interface.

Connection diagram for PM230 Power Module with or without integrated line filter class A or B

Power components that are optionally available depending on the Power Module used

The following line-side and load-side power components are optionally available in the appropriate frame sizes for the Power Modules:

 

Frame size

 

FSA

FSB

FSC

FSD

FSE

FSF

PM230 Power Module (IP54/IP55)

Available frame sizes

✓ 

✓ 

✓ 

✓ 

✓ 

✓ 

Line-side power components

Line filter class A

I

I

I

I

I

I

Line filter class B

I

I

I

I

I

I

Line reactor 1)

– 1)

– 1)

– 1)

– 1)

– 1)

– 1)

Load-side power components

Output reactor

S

S

S

S

S

S

Sine-wave filter

S

S

S

PM230 Power Module (IP20)

Available frame sizes

✓ 

✓ 

✓ 

✓ 

✓ 

✓ 

Line-side power components

Line filter class A

F

F

F

F

F

F

Line filter class B

2)

2)

2)

S

S

S

Line reactor 1)

– 1)

– 1)

– 1)

– 1)

– 1)

– 1)

Load-side power components

Output reactor

S

S

S

S

S

S

Sine-wave filter

S

S

S

 

U = Base component

S = Lateral mounting

I = Integrated

F = Power Modules available with and without integrated filter class A

– = Not possible

1) A line reactor is not required and must not be used in conjunction with a PM230 Power Module.

2) Lateral mounting is the only possible option for Push Through variants.

Maximum permissible cable lengths from the motor to the inverter when using output reactors or filters depending on the voltage range and the Power Module being used

The following load-side power components in the appropriate frame sizes are optionally available for the Power Modules and result in the following maximum cable lengths:

 

Maximum permissible motor cable lengths (shielded/unshielded) in m (ft)

Frame size

FSA

FSB

FSC

FSD

FSE

FSF

PM230 Power Module, degree of protection IP20

Available frame sizes

✓ 

✓ 

✓ 

✓ 

✓ 

✓ 

Without output reactor/sine-wave filter

25/100 (82/328)

25/100 (82/328)

25/100 (82/328)

25/100 (82/328)

25/100 (82/328)

25/100 (82/328)

With optional output reactor

 

 

 

 

 

 

  • At 380 ... 415 V 3 AC

150/225 (492/738)

150/225 (492/738)

150/225 (492/738)

  • At 440 ... 480 V 3 AC

100/150 (328/492)

100/150 (328/492)

100/150 (328/492)

  • At 380 ... 480 V 3 AC

200/300 (656/984)

200/300 (656/984)

200/300 (656/984)

With optional sine-wave filter

 

 

 

 

 

 

  • At 380 ... 480 V 3 AC

200/300 (656/984)

200/300 (656/984)

200/300 (656/984)

With integrated line filter class A
(EMC category C3)

 

 

 

 

 

 

  • At 380 ... 480 V 3 AC

50/- (164/-)

50/- (164/-)

50/- (164/-)

50/- (164/-)

50/- (164/-)

50/- (164/-)

With optional external line filter class B (EMC category C1 1), with unfiltered Power Module, maintains the limit values acc. to EN 61800‑3)

 

 

 

 

 

 

  • At 380 ... 480 V 3 AC

50/- (164/-)

50/- (164/-)

50/- (164/-)

50/- (164/-)

50/- (164/-)

50/- (164/-)

With optional external line filter class B and output reactor (EMC category C2 1), with unfiltered Power Module, maintains the limit values acc. to EN 61800‑3)

 

 

 

 

 

 

  • At 380 ... 415 V 3 AC

150/- (492/-)

150/- (492/-)

150/- (492/-)

  • At 440 ... 480 V 3 AC

100/- (328/-)

100/- (328/-)

100/- (328/-)

 

1) Additional information is available on the Internet at http://www.siemens.com/sinamics-g120/documentation

 

Technical specifications

General technical specifications

 

PM230 Power Modules

Degree of protection

IP55 (with BOP‑2 or blanking cover)
IP54 with IOP

IP20/UL Open Type
(Standard or Push Through variants)

Power (low overload LO)

0.37 ... 90 kW

0.37 ... 75 kW

Rated output current (low overload LO)

1.3 ... 178 A

1.3 ... 145 A

Power (high overload HO)

0.25 ... 75 kW

0.25 ... 55 kW

Rated output current (high overload HO)

0.9 ... 145 A

0.9 ... 110 A

System operating voltage

380 ... 480 V ±10 % 3 AC

Grid requirement
Short-circuit power RSC

>100

Input frequency

47 ... 63 Hz

Output frequency

 

  • Control mode U/f

0 ... 550 Hz

  • Control type Vector

0 ... 240 Hz

Pulse frequency

4 kHz
for higher pulse frequencies up to 16 kHz, see derating data

Power factor λ

0.9

Output voltage, max.

as % of input voltage

95 %

Overload capability

 

  • Low overload (LO)

Note: When the overload capability is used, the base-load current IL is not reduced.

  • Frame sizes FSA to FSC

1.5 × base-load current IL (i. e. 150 % overload) for 3 s plus
1.1 × base-load current IL (i. e. 110 % overload) for 57 s within a cycle time of 300 s

  • Frame sizes FSD to FSF

1.1 × base-load current IL (i. e. 110 % overload) for 60 s within a cycle time of 300 s

  • High overload (HO)

Note: When the overload capability is used, the base-load current IH is not reduced.

  • Frame sizes FSA to FSC

2 × base-load current IH (i. e. 200 % overload) for 3 s plus
1.5 × base-load current IH (i. e. 150 % overload) for 57 s within a cycle time of 300 s

  • Frame sizes FSD to FSF

1.5 × base-load current IH (i. e. 150 % overload) for 60 s within a cycle time of 300 s

Electromagnetic compatibility

  • Devices with line filter class A for applications according to Categories C3 and C2
  • Devices with line filter class B for applications according to Category C2 and compliance with conducted interference requirements of Category C1
  • Devices without line filter
  • Devices with line filter class A for applications according to Categories C3 and C2
  • Devices with line filter class B for applications according to Category C2 and compliance with conducted interference requirements of Category C1

Possible braking methods

DC braking

Operating temperature

 

  • Low overload (LO)

Frame sizes FSA to FSC: -10 ... +40 °C (14 ... 104 °F) without derating
Frame sizes FSD to FSF: 0 ... 40 °C (32 ... 104 °F) without derating

>40 ... 60 °C (104 ... 140 °F) see derating characteristics

  • High overload (HO)

Frame sizes FSA to FSC: -10 ... +50 °C (14 ... 122 °F) without derating
Frame sizes FSD to FSF: 0 ... 50 °C (32 ... 122 °F) without derating

>50 ... 60 °C (122 ... 140 °F) see derating characteristics

Relative humidity

<95 %, condensation not permissible

Storage temperature

-40 ... +70 °C (-40 ... +158 °F)

Cooling

Power units with increased air cooling using integrated fans

Installation altitude

Up to 1000 m (3281 ft) above sea level without derating,
> 1000 m (3281 ft) see derating characteristics

Protection functions

  • Undervoltage
  • Overvoltage
  • Overcurrent/overload
  • Overtemperature
  • Ground fault
  • Short-circuit
  • Stall protection
  • Motor blocking protection
  • Motor overtemperature
  • Inverter overtemperature
  • Parameter locking

Rated short-circuit current SCCR (Short-Circuit Current Rating) 3)

Frame sizes FSA to FSC: 40 kA

65 kA

Compliance with standards

UL 1), cUL 2), CE, RCM, SEMI F47

CE marking

According to Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU

 

1) For degree of protection IP55/UL Type 12, the UL approval only applies to frame sizes FSA to FSC.

2) Applies to PM230 Power Modules, frame sizes FSA to FSC.

3) Applies to industrial control panel installations acc. to NEC Article 409 or UL 508A/508C.

 

PM230 Power Modules, degree of protection IP55

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules, degree of protection IP55/UL Type 12

With integrated line filter class A

6SL3223-0DE13-7AG1

6SL3223-0DE15-5AG1

6SL3223-0DE17-5AG1

6SL3223-0DE21-1AG1

6SL3223-0DE21-5AG1

With integrated line filter class B

6SL3223-0DE13-7BG1

6SL3223-0DE15-5BG1

6SL3223-0DE17-5BG1

6SL3223-0DE21-1BG1

6SL3223-0DE21-5BG1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated1)

A

1.3

1.7

2.2

3.1

4.1

  • Base-load current IL1)

A

1.3

1.7

2.2

3.1

4.1

  • Base-load current IH2)

A

0.9

1.3

1.7

2.2

3.1

  • Maximum current Imax

A

2

2.6

3.4

4.7

6.2

Rated power

 

 

 

 

 

 

  • Based on IL

kW

0.37

0.55

0.75

1.1

1.5

  • Based on IH

kW

0.25

0.37

0.55

0.75

1.1

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency η

%

86

90

92

94

95

Power loss 3)

at rated current

kW

0.04

0.043

0.047

0.055

0.064

Cooling air requirement

m3/s (ft3/s)

0.007 (0.25)

0.007 (0.25)

0.007 (0.25)

0.007 (0.25)

0.007 (0.25)

Sound pressure level

LpA (1 m)

dB

61.9

61.9

61.9

61.9

61.9

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

1.3

1.8

2.3

3.2

4.2

  • Based on IH

A

0.9

1.3

1.8

2.3

3.2

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection 6)

 

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

154 (6.06)

154 (6.06)

154 (6.06)

154 (6.06)

154 (6.06)

  • Height

mm (in)

460 (18.11)

460 (18.11)

460 (18.1)

460 (18.11)

460 (18.1)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

249 (9.80)

249 (9.80)

249 (9.80)

249 (9.80)

249 (9.80)

  • With operator panel, max.

mm (in)

266 (10.47)

266 (10.47)

266 (10.47)

266 (10.47)

266 (10.47)

Frame size

 

FSA

FSA

FSA

FSA

FSA

Weight, approx.

kg (lb)

4.3 (9.48)

4.3 (9.48)

4.3 (9.48)

4.3 (9.48)

4.3 (9.48)

 

1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800‑3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.

6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For more information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules, degree of protection IP55/UL Type 12

With integrated line filter class A

6SL3223-0DE22-2AG1

6SL3223-0DE23-0AG1

6SL3223-0DE24-0AG1

6SL3223-0DE25-5AG1

6SL3223-0DE27-5AG1

With integrated line filter class B

6SL3223-0DE22-2BG1

6SL3223-0DE23-0BG1

6SL3223-0DE24-0BG1

6SL3223-0DE25-5BG1

6SL3223-0DE27-5BG1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated1)

A

5.9

7.7

10.2

13.2

18

  • Base-load current IL1)

A

5.9

7.7

10.2

13.2

18

  • Base-load current IH2)

A

4.1

5.9

7.7

10.2

13.2

  • Maximum current Imax

A

8.9

11.8

15.4

20.4

27

Rated power

 

 

 

 

 

 

  • Based on IL

kW

2.2

3

4

5.5

7.5

  • Based on IH

kW

1.5

2.2

3

4

5.5

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency η

%

96

96

97

97

97

Power loss 3)

at rated current

kW

0.086

0.11

0.137

0.173

0.235

Cooling air requirement

m3/s (ft3/s)

0.007 (0.25)

0.007 (0.25)

0.009 (0.32)

0.009 (0.32)

0.009 (0.32)

Sound pressure level

LpA (1 m)

dB

61.9

61.9

62.8

62.8

62.8

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

6.1

8

11

14

19

  • Based on IH

A

4.2

6.1

8

11

14

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

2.5 ... 6

4 ... 6

4 ... 6

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

2.5 ... 6

4 ... 6

4 ... 6

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection 6)

 

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

154 (6.06)

154 (6.06)

180 (7.09)

180 (7.09)

180 (7.09)

  • Height

mm (in)

460 (18.11)

460 (18.11)

540 (21.26)

540 (21.26)

540 (21.26)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

249 (9.80)

249 (9.80)

249 (9.80)

249 (9.80)

249 (9.80)

  • With operator panel, max.

mm (in)

266 (10.47)

266 (10.47)

266 (10.47)

266 (10.47)

266 (10.47)

Frame size

 

FSA

FSA

FSB

FSB

FSB

Weight, approx.

kg (lb)

4.3 (9.48)

4.3 (9.48)

6.3 (13.9)

6.3 (13.9)

6.3 (13.9)

 

1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800‑3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.

6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For more information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules, degree of protection IP55/UL Type 12 1)

With integrated line filter class A

6SL3223-0DE31-1AG1

6SL3223-0DE31-5AG1

6SL3223-0DE31-8AG1

6SL3223-0DE32-2AA0

6SL3223-0DE33-0AA0

With integrated line filter class B

6SL3223-0DE31-1BG1

6SL3223-0DE31-5BG1

6SL3223-0DE31-8BA0

6SL3223-0DE32-2BA0

6SL3223-0DE33-0BA0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

 

  • Rated current Irated2)

A

26

32

38

38

45

60

  • Base-load current IL 2)

A

26

32

38

38

45

60

  • Base-load current IH 3)

A

18

26

32

32

38

45

  • Maximum current Imax

A

39

52

64

48

57

67

Rated power

 

 

 

 

 

 

 

  • Based on IL

kW

11

15

18.5

18.5

22

30

  • Based on IH

kW

7.5

11

15

15

18.5

22

Rated pulse frequency

kHz

4

4

4

4

4

4

Efficiency η

%

97

97

98

97

97

97

Power loss 4)

at rated current

kW

0.299

0.365

0.435

0.478

0.569

0.784

Cooling air requirement

m3/s (ft3/s)

0.02 (0.7)

0.02 (0.7)

0.02 (0.7)

0.039 (1.4)

0.039 (1.4)

0.039 (1.4)

Sound pressure level

LpA (1 m)

dB

66.1

66.1

66.1

56

56

56

24 V DC power supply

for Control Unit

A

1

1

1

1

1

1

Input current 5)

 

 

 

 

 

 

 

  • Rated current

A

27

33

39

39

42

56

  • Based on IH

A

19

27

33

33

36

42

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

M6 screw studs

M6 screw studs

M6 screw studs

  • Conductor cross-section

mm2

6 ... 16

10 ... 16

10 ... 16

16 ... 35

16 ... 35

16 ... 35

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

M6 screw studs

M6 screw studs

M6 screw studs

  • Conductor cross-section

mm2

6 ... 16

10 ... 16

10 ... 16

16 ... 35

16 ... 35

16 ... 35

Motor cable length, max. 6)

 

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection 7)

 

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

IP55

IP55

IP55

Dimensions

 

 

 

 

 

 

 

  • Width

mm (in)

230 (9.06)

230 (9.06)

230 (9.06)

320 (12.60)

320 (12.60)

320 (12.60)

  • Height

mm (in)

620 (24.41)

620 (24.41)

620 (24.41)

640 (25.20)

640 (25.20)

640 (25.20)

  • Depth

 

 

 

 

 

 

 

  • Without operator panel

mm (in)

249 (9.80)

249 (9.80)

249 (9.80)

329 (12.95)

329 (12.95)

329 (12.95)

  • With operator panel, max.

mm (in)

266 (10.47)

266 (10.47)

266 (10.47)

346 (13.62)

346 (13.62)

346 (13.62)

Frame size

 

FSC

FSC

FSC

FSD

FSD

FSD

Weight, approx.

kg (lb)

9.5 (20.95)

9.5 (20.95)

9.5 (20.95)

31 (68.36)

31 (68.36)

31 (68.36)

 

1) UL Type 12 only for frame size FSC

2) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

3) The base-load current IH is based on the duty cycle for high overload (HO).

4) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311

5) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

6) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800‑3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.

7) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For more information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules, degree of protection IP55

With integrated line filter class A

6SL3223-0DE33-7AA0

6SL3223-0DE34-5AA0

6SL3223-0DE35-5AA0

6SL3223-0DE37-5AA0

6SL3223-0DE38-8AA0

With integrated line filter class B

6SL3223-0DE33-7BA0

6SL3223-0DE34-5BA0

6SL3223-0DE35-5BA0

6SL3223-0DE37-5BA0

6SL3223-0DE38-8BA0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated1)

A

75

90

110

145

178

  • Base-load current IL1)

A

75

90

110

145

178

  • Base-load current IH2)

A

60

75

90

110

145

  • Maximum current Imax

A

90

112

135

165

217

Rated power

 

 

 

 

 

 

  • Based on IL

kW

37

45

55

75

90

  • Based on IH

kW

30

37

45

55

75

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency η

%

97

97

97

97

97

Power loss 3)

at rated current

kW

0.855

1.073

1.122

1.542

1.98

Cooling air requirement

m3/s (ft3/s)

0.039 (1.4)

0.039 (1.4)

0.117 (4.1)

0.117 (4.1)

0.117 (4.1)

Sound pressure level

LpA (1 m)

dB

56

56

61

61

61

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

70

84

102

135

166

  • Based on IH

A

56

70

84

102

135

Line supply connection

U1/L1, V1/L2, W1/L3

 

M6 screw studs

M6 screw studs

M8 screw studs

M8 screw studs

M8 screw studs

  • Conductor cross-section

mm2

25 ... 50

25 ... 50

35 ... 120

35 ... 120

35 ... 120

Motor connection

U2, V2, W2

 

M6 screw studs

M6 screw studs

M8 screw studs

M8 screw studs

M8 screw studs

  • Conductor cross-section

mm2

25 ... 50

25 ... 50

35 ... 120

35 ... 120

35 ... 120

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection 6)

 

IP55

IP55

IP55

IP55

IP55

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

320 (12.60)

320 (12.60)

410 (16.14)

410 (16.14)

410 (16.14)

  • Height

mm (in)

751 (29.57)

751 (29.57)

915 (36.02)

915 (36.02)

915 (36.02)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

329 (12.95)

329 (12.95)

416 (16.38)

416 (16.38)

416 (16.38)

  • With operator panel, max.

mm (in)

346 (13.62)

346 (13.62)

433 (17.05)

433 (17.05)

433 (17.05)

Frame size

 

FSE

FSE

FSF

FSF

FSF

Weight, approx.

kg (lb)

37 (81.6) (with filter cl. A)
38 (83.8) (with filter cl. B)

37 (81.6) (with filter cl. A)
38 (83.8) (with filter cl. B)

70 (154)

70 (154)

70 (154)

 

1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800‑3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.

6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55. For more information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.

 

PM230 Power Modules degree of protection IP20 Standard variant

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 Standard variant

Without integrated line filter

6SL3210-1NE11-3UG1

6SL3210-1NE11-7UG1

6SL3210-1NE12-2UG1

6SL3210-1NE13-1UG1

6SL3210-1NE14-1UG1

With integrated line filter class A

6SL3210-1NE11-3AG1

6SL3210-1NE11-7AG1

6SL3210-1NE12-2AG1

6SL3210-1NE13-1AG1

6SL3210-1NE14-1AG1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated1)

A

1.3

1.7

2.2

3.1

4.1

  • Base-load current IL1)

A

1.3

1.7

2.2

3.1

4.1

  • Base-load current IH2)

A

0.9

1.3

1.7

2.2

3.1

  • Maximum current Imax

A

2

2.6

3.4

4.7

6.2

Rated power

 

 

 

 

 

 

  • Based on IL

kW

0.37

0.55

0.75

1.1

1.5

  • Based on IH

kW

0.25

0.37

0.55

0.75

1.1

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency η

%

89

93

93

94

95

Power loss 3)

at rated current

kW

0.031

0.034

0.041

0.049

0.06

Cooling air requirement

m3/s (ft3/s)

0.002 (0.1)

0.002 (0.1)

0.005 (0.2)

0.005 (0.2)

0.005 (0.2)

Sound pressure level

LpA (1 m)

dB

<50

<50

<50

<50

<50

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

1.3

1.8

2.3

3.2

4.2

  • Based on IH

A

0.9

1.3

1.8

2.3

3.2

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

73 (2.87)

73 (2.87)

73 (2.87)

73 (2.87)

73 (2.87)

  • Height

mm (in)

196 (7.72)

196 (7.72)

196 (7.72)

196 (7.72)

196 (7.72)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

  • With operator panel, max.

mm (in)

245 (9.65)

245 (9.65)

245 (9.65)

245 (9.65)

245 (9.65)

Frame size

 

FSA

FSA

FSA

FSA

FSA

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

  • With integrated line filter

kg (lb)

1.6 (3.53)

1.6 (3.53)

1.6 (3.53)

1.6 (3.53)

1.6 (3.53)

 

1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 Standard variant

Without integrated line filter

6SL3210-1NE15-8UG1

6SL3210-1NE17-7UG1

6SL3210-1NE21-0UG1

6SL3210-1NE21-3UG1

6SL3210-1NE21-8UG1

With integrated line filter class A

6SL3210-1NE15-8AG1

6SL3210-1NE17-7AG1

6SL3210-1NE21-0AG1

6SL3210-1NE21-3AG1

6SL3210-1NE21-8AG1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated1)

A

5.9

7.7

10.2

13.2

18

  • Base-load current IL1)

A

5.9

7.7

10.2

13.2

18

  • Base-load current IH2)

A

4.1

5.9

7.7

10.2

13.2

  • Maximum current Imax

A

8.9

11.8

15.4

20.4

27

Rated power

 

 

 

 

 

 

  • Based on IL

kW

2.2

3

4

5.5

7.5

  • Based on IH

kW

1.5

2.2

3

4

5.5

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency η

%

96

96

97

97

97

Power loss 3)

at rated current

kW

0.078

0.102

0.13

0.165

0.224

Cooling air requirement

m3/s (ft3/s)

0.005 (0.2)

0.005 (0.2)

0.009 (0.3)

0.009 (0.3)

0.009 (0.3)

Sound pressure level

LpA (1 m)

dB

<50

<50

<62

<62

<62

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

6.1

8

11

14

19

  • Based on IH

A

4.2

6.1

8

11

14

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

1.5 ... 2.5

1.5 ... 6

1.5 ... 6

1.5 ... 6

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

1.5 ... 2.5

1.5 ... 6

1.5 ... 6

1.5 ... 6

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

73 (2.87)

73 (2.87)

100 (328.10)

100 (328.10)

100 (328.10)

  • Height

mm (in)

196 (7.72)

196 (7.72)

292 (11.50)

292 (11.50)

292 (11.50)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

  • With operator panel, max.

mm (in)

245 (9.65)

245 (9.65)

245 (9.65)

245 (9.65)

245 (9.65)

Frame size

 

FSA

FSA

FSB

FSB

FSB

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

1.4 (3.09)

1.4 (3.09)

2.8 (6.17)

2.8 (6.17)

2.8 (6.17)

  • With integrated line filter

kg (lb)

1.6 (3.53)

1.6 (3.53)

3 (6.61)

3 (6.61)

3 (6.61)

 

1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 Standard variant

Without integrated line filter

6SL3210-
1NE22-6UG1

6SL3210-
1NE23-2UG1

6SL3210-
1NE23-8UG1

6SL3210-
1NE24-5UL0

6SL3210-
1NE26-0UL0

With integrated line filter class A

6SL3210-
1NE22-6AG1

6SL3210-
1NE23-2AG1

6SL3210-
1NE23-8AG1

6SL3210-
1NE24-5AL0

6SL3210-
1NE26-0AL0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated1)

A

26

32

38

45

60

  • Base-load current IL1)

A

26

32

38

45

60

  • Base-load current IH2)

A

18

26

32

38

45

  • Maximum current Imax

A

39

52

64

57

67

Rated power

 

 

 

 

 

 

  • Based on IL

kW

11

15

18.5

22

30

  • Based on IH

kW

7.5

11

15

18.5

22

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency η

%

97

97

98

98

97

Power loss 3)

at rated current

kW

0.291

0.355

0.423

0.539

0.726

Cooling air requirement

m3/s (ft3/s)

0.019 (0.7)

0.019 (0.7)

0.019 (0.7)

0.08 (2.8)

0.08 (2.8)

Sound pressure level

LpA (1 m)

dB

<65

<65

<65

<60

<60

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

27

33

39

42

56

  • Based on IH

A

19

27

33

36

42

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

M6 screw studs

M6 screw studs

  • Conductor cross-section

mm2

6 ... 16

6 ... 16

6 ... 16

16 ... 35

16 ... 35

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

M6 screw studs

M6 screw studs

  • Conductor cross-section

mm2

6 ... 16

6 ... 16

6 ... 16

16 ... 35

16 ... 35

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

140 (5.51)

140 (5.51)

140 (5.51)

275 (10.83)

275 (10.83)

  • Height

 

 

 

 

 

 

  • Without integrated line filter

mm (in)

355 (13.98)

355 (13.98)

355 (13.98)

419 (16.50)

419 (16.50)

  • With integrated line filter

mm (in)

355 (13.98)

355 (13.98)

355 (13.98)

512 (20.16)

512 (20.16)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

165 (6.50)

204 (8.03)

204 (8.03)

  • With operator panel, max.

mm (in)

245 (9.65)

245 (9.65)

245 (9.65)

275 (10.83)

275 (10.83)

Frame size

 

FSC

FSC

FSC

FSD

FSD

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

4.5 (9.92)

4.5 (9.92)

4.5 (9.92)

11 (24.3)

11 (24.3)

  • With integrated line filter

kg (lb)

5.1 (11.25)

5.1 (11.25)

5.1 (11.25)

14 (30.87)

14 (30.87)

 

1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 Standard variant

Without integrated line filter

6SL3210-1NE27-5UL0

6SL3210-1NE28-8UL0

6SL3210-1NE31-1UL0

6SL3210-1NE31-5UL0

With integrated line filter class A

6SL3210-1NE27-5AL0

6SL3210-1NE28-8AL0

6SL3210-1NE31-1AL0

6SL3210-1NE31-5AL0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

  • Rated current Irated1)

A

75

90

110

145

  • Base-load current IL1)

A

75

90

110

145

  • Base-load current IH2)

A

60

75

90

110

  • Maximum current Imax

A

90

112

135

165

Rated power

 

 

 

 

 

  • Based on IL

kW

37

45

55

75

  • Based on IH

kW

30

37

45

55

Rated pulse frequency

kHz

4

4

4

4

Efficiency η

%

97

97

97

97

Power loss 3)

at rated current

kW

0.791

0.976

1.237

1.69

Cooling air requirement

m3/s (ft3/s)

0.08 (2.8)

0.08 (2.8)

0.15 (5.3)

0.15 (5.3)

Sound pressure level

LpA (1 m)

dB

<60

<60

<60

<60

24 V DC power supply

for Control Unit

A

1

1

1

1

Input current 4)

 

 

 

 

 

  • Rated current

A

70

84

102

135

  • Based on IH

A

56

70

84

102

Line supply connection

U1/L1, V1/L2, W1/L3

 

M6 screw studs

M6 screw studs

M8 screw studs

M8 screw studs

  • Conductor cross-section

mm2

25 ... 50

25 ... 50

35 ... 120

35 ... 120

Motor connection

U2, V2, W2

 

M6 screw studs

M6 screw studs

M8 screw studs

M8 screw studs

  • Conductor cross-section

mm2

25 ... 50

25 ... 50

35 ... 120

35 ... 120

Motor cable length, max. 5)

 

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

  • Width

mm (in)

275 (10.83)

275 (10.83)

350 (13.78)

350 (13.78)

  • Height

 

 

 

 

 

  • Without integrated line filter

mm (in)

499 (19.65)

499 (19.65)

634 (24.96)

634 (24.96)

  • With integrated line filter

mm (in)

635 (25)

635 (25)

934 (36.77)

934 (36.77)

  • Depth

 

 

 

 

 

  • Without operator panel

mm (in)

204 (8.03)

204 (8.03)

316 (12.44)

316 (12.44)

  • With operator panel, max.

mm (in)

275 (10.83)

275 (10.83)

387 (15.24)

387 (15.24)

Frame size

 

FSE

FSE

FSF

FSF

Weight, approx.

 

 

 

 

 

  • Without integrated line filter

kg (lb)

15 (33.1)

15 (33.1)

34 (74.97)

34 (74.97)

  • With integrated line filter

kg (lb)

22 (48.5)

22 (48.5)

46 (101.43)

46 (101.43)

 

1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.

 

PM230 Power Modules degree of protection IP20 Push Through variant

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 Push Through variant

Without integrated line filter

6SL3211-1NE17-7UG1

6SL3211-1NE21-8UG1

6SL3211-1NE23-8UG1

With integrated line filter class A

6SL3211-1NE17-7AG1

6SL3211-1NE21-8AG1

6SL3211-1NE23-8AG1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

  • Rated current Irated1)

A

7.7

18

38

  • Base-load current IL1)

A

7.7

18

38

  • Base-load current IH2)

A

5.9

13.2

32

  • Maximum current Imax

A

11.8

27

64

Rated power

 

 

 

 

  • Based on IL

kW

3

7.5

18.5

  • Based on IH

kW

2.2

5.5

15

Rated pulse frequency

kHz

4

4

4

Efficiency η

%

96

97

98

Power loss 3)

at rated current

kW

0.102

0.224

0.423

Cooling air requirement

m3/s (ft3/s)

0.005 (0.2)

0.009 (0.3)

0.019 (0.7)

Sound pressure level

LpA (1 m)

dB

<56

<62

<65

24 V DC power supply

for Control Unit

A

1

1

1

Input current 4)

 

 

 

 

  • Rated current

A

8

19

39

  • Based on IH

A

6.1

14

33

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

4 ... 6

6 ... 16

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

4 ... 6

10 ... 16

Motor cable length, max. 5)

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

Dimensions

 

 

 

 

  • Width

mm (in)

126 (4.96)

154 (6.06)

200 (7.87)

  • Height

mm (in)

238 (9.37)

345 (13.58)

411 (16.18)

  • Depth

 

 

 

 

  • Without operator panel

mm (in)

171 (6.73)

171 (6.73)

171 (6.73)

  • With operator panel, max.

mm (in)

251 (9.88)

251 (9.88)

251 (9.88)

Frame size

 

FSA

FSB

FSC

Weight, approx.

With integrated line filter

 

 

 

 

  • Without integrated line filter

kg (lb)

1.7 (3.75)

3.4 (7.50)

5.4 (11.91)

  • With integrated line filter

kg (lb)

1.9 (4.19)

3.6 (7.94)

6 (13.23)

 

1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.
 

Characteristic curves

Derating data

Pulse frequency

Rated power 1)

Rated output current in A

for a pulse frequency of

400 V

460 V

kW

hp

4 kHz

6 kHz

8 kHz

10 kHz

12 kHz

14 kHz

16 kHz

0.37

0.5

1.3

1.11

0.91

0.78

0.65

0.59

0.52

0.55

0.5

1.7

1.45

1.19

1.02

0.85

0.77

0.68

0.75

0.75

2.2

1.87

1.54

1.32

1.1

0.99

0.88

1.1

1

3.1

2.64

2.17

1.86

1.55

1.4

1.24

1.5

2

4.1

3.49

2.87

2.46

2.05

1.85

1.64

2.2

3

5.9

5.02

4.13

3.54

2.95

2.66

2.36

3

3

7.7

6.55

5.39

4.62

3.85

3.47

3.08

4

5

10.2

8.67

7.14

6.12

5.1

4.59

4.08

5.5

7.5

13.2

11.22

9.24

7.92

6.6

5.94

5.28

7.5

10

18

15.3

12.6

10.8

9

8.1

7.2

11

15

26

22.1

18.2

15.6

13

11.7

10.4

15

15

32

27.2

22.4

19.2

16

14.4

12.8

18.5

20

38

32.3

26.6

22.8

19

17.1

15.2

22

25

45

38.25

31.5

27

22.5

20.25

18

30

30

60

51

42

36

30

27

24

37

40

75

63.75

52.5

45

37.5

33.75

30

45

50

90

76.5

63

54

45

40.5

36

55

60

110

93.5

77

66 2)

55 2)

49.5 2)

44 2)

75

75

145

123.3

101.5

90

100

178

151.3

124.6

 

1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO).

2) Values apply only to IP20 variants.

 

Ambient temperature

Permissible output current as a function of the ambient temperature for low overload (LO) for PM230 Power Modules, frame sizes FSA to FSC

 

Permissible output current as a function of ambient temperature for low overload (LO) for PM230 Power Modules, frame sizes FSD to FSF

 

Permissible output current as a function of ambient temperature for high overload (HO) PM230 Power Modules, frame sizes FSA to FSC

 

Permissible output current as a function of ambient temperature for high overload (HO) PM230 Power Modules, frame sizes FSD to FSF

Note:

The operating temperature ranges of the Control Units should be taken into account. The temperature ranges are specified in the section Technical specifications under Control Units.

Installation altitude

Permissible line supplies as a function of the installation altitude

  • Installation altitude up to 2000 m (6562 ft) above sea level
    • Connection to every supply system permitted for the inverter
  • Installation altitudes between 2000 m (6562 ft) and 4000 m (13124 ft) above sea level
    • Connection to a TN system with grounded neutral point
    • TN systems with grounded line conductor are not permitted
    • The TN line system with grounded neutral point can also be supplied using an isolation transformer
    • The phase-to-phase voltage does not have to be reduced

Note:

The connected motors, power elements and components must be considered separately.

Permissible output current as a function of the installation altitude for PM230 Power Modules, frame sizes FSA to FSF

 

System operating voltage

Permissible output current as a function of the line voltage for PM230 Power Modules, frame sizes FSA to FSF

 

Permissible rated power as a function of the line voltage for PM230 Power Modules, frame sizes FSA to FSF

 

Dimensional drawings

PM230 Power Modules, degree of protection IP55

Principle dimension drawing and drill pattern for PM230 Power Modules, degree of protection IP55, with integrated line filter class A/B

Frame size

Dimensions

in mm (inches)

Drilling dimensions

in mm (inches)

Cooling clearance

in mm (inches)

Mounting

 

a
(width)

b
(height)

c
(depth) 1)

d

e

f

top

bottom

side

With bolts, nuts and washers

PM230 Power Modules, degree of protection IP55 with integrated line filter class A/B

FSA

154
(6.06)

460
(18.11)

249
(9.8)

132
(5.19)

445
(17.51)

11
(0.43)

100
(3.94)

0
(0)

0
(0)

4 × M4

FSB

180
(7.08)

540
(21.25)

249
(9.8)

158
(5.9)

524
(20.62)

11
(0.43)

100
(3.94)

0
(0)

0
(0)

4 × M4

FSC

230
(9.05)

620
(24.4)

249
(9.8)

208
(8.18)

604
(23.77)

11
(0.43)

125
(4.92)

0
(0)

0
(0)

4 × M5

FSD

320
(12.59)

640
(25.19)

329
(12.95)

285
(11.22)

600
(23.62)

17.5
(0.69)

300
(11.81)

0
(0)

50
(1.97) 2)

4 × M8

FSE

320
(12.59)

751
(29.56)

329
(12.95)

285
(11.22)

710
(27.95)

17.5
(0.69)

300
(11.81)

0
(0)

50
(1.97) 2)

4 × M8

FSF

410
(16.14)

915
(36.02)

416
(16.38)

370
(14.56)

870
(34.25)

20
(0.79)

350
(13.78)

0
(0)

50
(1.97) 2)

4 × M8

 

1) Increased depth:

• When the IOP is plugged on, the depth increases by 17 mm (0.67 in)

• When the BOP‑2/blanking cover is plugged on, the depth increases by 7 mm (0.28 in)

2) Up to 40 °C (104 °F) without any lateral clearance.

 

PM230 Power Modules, degree of protection IP20, Standard variant

Principle dimension drawing and drill pattern for PM230 Power Modules, degree of protection IP20, Standard variant, with/without integrated line filter class A

Frame size

Dimensions

in mm (inches)

Drilling dimensions

in mm (inches)

Cooling clearance

in mm (inches)

Mounting

 

a
(width)

b
(height)

c
(depth) 1)

d

e

f

top

bottom

side 2)

With bolts

PM230 Power Modules, degree of protection IP20, Standard variant, with/without integrated line filter class A

FSA

73
(2.87)

196
(7.72)

165
(6.5)

62.3
(2.45)

186
(7.32)

6
(0.24)

80
(3.15)

100
(3.94)

0
(0)

3 × M4

FSB

100
(3.94)

292
(11.5)

165
(6.5)

80
(3.15)

281
(11.06)

6
(0.24)

80
(3.15)

100
(3.94)

0
(0)

4 × M4

FSC

140
(5.51)

355
(13.98)

165
(6.5)

120
(4.72)

343
(13.5)

6
(0.24)

80
(3.15)

100
(3.94)

0
(0)

4 × M5

FSD

275
(10.83)

419/512
(16.50/20.16)

204
(8.03)

235
(9.25)

325/419
(12.8/16.5)

11
(0.43)

300
(11.81)

300
(11.81)

0
(0)

4 x M6

FSE

275
(10.83)

499/635
(19.65/25)

204
(8.03)

235
(9.25)

405/541
(15.94/21.3)

11
(0.43)

300
(11.81)

300
(11.81)

0
(0)

4 x M6

FSF

350
(13.78)

634/934
(24.96/36.77)

316
(12.44)

300
(11.81)

598/899
(23.54/35.39)

11
(0.43)

350
(13.78)

350
(13.78)

0
(0)

4 × M8

 

1) Increased depth:

• When the CU230P-2 Control Unit is plugged on, the depth increases by 58 mm (2.28 in) for FSA to FSC and by 49 mm (1.93 in) for FSD to FSF

• When the IOP is plugged on, the depth increases by a further 22 mm (0.87 in)

• When the BOP‑2 is plugged on, the depth increases by a further 12 mm (0.47 in)

2)The Power Modules can be mounted side by side. A side clearance of 1 mm (0.04 in) is recommended for tolerance-related reasons.

 

PM230 Power Modules, degree of protection IP20, Push Through variant

Principle dimension drawing and drill pattern for PM230 Power Modules, degree of protection IP20, Push Through variant, with/without integrated line filter class A

Frame size

Dimensions

in mm (inches)

Drilling dimensions

in mm (inches)

Section of cabinet

in mm (inches)

Cooling clearance

in mm (inches)

Mounting

 

a
(width)

b
(height)

c
(depth) 1)

d

e

f

g
(width)

h
(height)

top

bottom

side 2)

With bolts

PM230 Power Modules, degree of protection IP20, Push Through variant, with/without integrated line filter class A

FSA

125.9
(4.96)

238
(9.37)

171
(6.73)

106
(4.17)

103
(4.06)

27
(1.06)

88
(3.46)

198
(7.8)

80
(3.15)

100
(3.94)

0
(0)

M5

FSB

153.9
(6.06)

345
(13.58)

171
(6.73)

134
(5.28)

147.5
(5.81)

34.5
(1.36)

116
(4.57)

304
(11.97)

80
(3.15)

100
(3.94)

0
(0)

M5

FSC

200
(7.87)

410.5
(16.16)

171
(6.73)

174
(6.85)

123
(4.84)

30.5
(1.2)

156
(6.14)

365
(14.37)

80
(3.15)

100
(3.94)

0
(0)

M5

 

1) Overall depth, of which 117.7 mm (4.63 in) is inside and 53.1 mm (2.09 in) is outside the control cabinet.

Increased depth:

• When the CU230P‑2 Control Unit is plugged on, the depth increases by 58 mm (2.28 in)

• When the IOP is plugged on, the depth increases by a further 22 mm (0.87 in)

• When the BOP‑2 is plugged on, the depth increases by a further 12 mm (0.47 in)

2)The Power Modules can be mounted side by side (mounting frame to mounting frame). A side clearance of 1 mm (0.04 in) is recommended for tolerance-related reasons.

 

(Nguyễn Thảo Trường - http://DienElectric.com theo Siemens)